E5C4&E5C2 Series Temperature Controller with Analog Setting knob

DIN-sized (48 x 48 mm) Temperature Controller with Analog Setting

1.Compact, low-cost Temperature Controller.

2.Incorporates proportional control and reset adjustment function.

3.Consecutive mounting possible using mounting adapter.

4.Incorporates a plug-in socket, thus allows to DIN-track and flush mounting.

Request a Quote

PRODUCTS DETAILS

6.jpg

E5C2, E5C4 Series Temperature Controllers

Model Number Structure

■ Model Number Legend

 1.E5C4&E5C2 Series Temperature Controller.jpg

1.Control Outputs

R: Relay

2.Control Method

20: ON-OFF control

40: Proportional control

3.Input

K: K-type thermocouple

J: J-type thermocouple

P-D: Platinum resistance thermometer (Pt100)

G: Thermistor with replaceable element

Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to Ordering Information when ordering.

Examples

1.Relay control output, ON/OFF control, type-K thermocouple input: E5C2-R20K

2.Relay control output, proportional control, thermocouple input: E5C2-R40P-D

 

Ordering Information

■ Temperature Controllers

 2.E5C4&E5C2 Series Temperature Controller.jpg

Note: When placing an order, specify the temperature range in addition to the model number.

 

Standard Models

 

 

 

Indication method

No indication

 

 

 

Control mode

ON/OFF

Proportional(P)

 

Input

 

Output

Relay

Input/standard scale(℃)

Thermocouple

K (CA)
Chromel
vs.alumel

0 to 200

E5C2-R20K

E5C2-R40K

0 to 300

E5C2-R20K

E5C2-R40K

0 to 400

E5C2-R20K

E5C2-R40K

0 to 600

E5C2-R20K

E5C2-R40K

0 to 800

E5C2-R20K

E5C2-R40K

0 to 1000

E5C2-R20K

---

0 to 1200

E5C2-R20K

---

J(IC)
Iron vs.
constantan

0 to 200

E5C2-R20J

---

0 to 300

E5C2-R20J

---

0 to 400

E5C2-R20J

---

 

 

 

 

Indication method

No indication

 

 

 

Control mode

ON/OFF

 

Input

 

Output

Relay

Input/standard scale(℃)

Resistance Thermometer

Platinum resistance thermometer Pt100

−50 to 50

E5C2-R20P-D

−20 to 80

E5C2-R20P-D

0 to 50

E5C2-R20P-D

0 to 100

E5C2-R20P-D

0 to 200

E5C2-R20P-D

0 to 300

E5C2-R20P-D

0 to 400

E5C2-R20P-D

Thermistor

THE (replaceable element)

−50 to 50

E5C2-R20G

0 to 100

E5C2-R20G

50 to 150

E5C2-R20G

100 to 200

E5C2-R20G

150 to 300

E5C2-R20G

 

■ Accessories (Order Separately)

Sockets

Name

Model

Front Connecting Socket

P2CF-08

Back Connecting Socket

P3G-08

Front Connecting Socket with Finger Protection

P2CF-08-E

Protective Cover (for finger protection)

Y92A-48G

 

Protective Cover

Type

Model

Hard Protective Cover

Y92A-48B

 

Specifications

■ Ratings

Supply voltage

100 to 240 VAC 50/60 Hz

Operating voltage range

90% to 110% of rated supply voltage

Power consumption

Approx. 3.6 VA

Input

Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor with replaceable element

Control method

ON/OFF or proportional control

Setting method

Analog setting

Indication method

No indication

Control output

Relay output:SPDT, 3 A at 250 VAC,resistive load (switching capacity: 330 VA)

Ambient operating temperature

−10°C to 55°C (with no icing or condensation)

Ambient operating humidity

45% to 85%

Note: Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)

 

■ Characteristics

Setting accuracy

±2% FS max.(Influence of EMS:±4% FS max.)(See note 1.)

Hysteresis

Approx. 0.5% FS (fixed)

Proportional band

3% FS (fixed)

Control period

Approx. 20s

Reset range

5±1% FS min.(See note 2.)

Insulation resistance

20 MΩ min.(at 500 VDC)

Dielectric strength

2,000 VAC,50/60 Hz for 1 min between charged terminals and uncharged metallic parts

Vibration resistance

Malfunction:10 to 55 Hz,0.15-mm single amplitude for 10 min each in X,Y,and Z directions
Destruction:16.7 Hz,2-mm double amplitude for 2 hrs each in X,Y,and Z directions

Shock resistance

Malfunction:147 m/s2,3 times each in 6 directions
Destruction:294 m/s2,3 times each in 6 directions

Life expectancy

Electrical:100,000 operations min.(3 A at 110 VAC,resistive load)

Weight

Approx. 100 g(with flush-mounting adapter)

Degree of protection

Front panel:IEC standard IP40 (See note 3.)
Terminals:IEC standard IP00

Applicable Socket

P2CF-08 (order separately),P3G-08 (order separately)

Applicable Protective Cover

Y92A-48B (order separately)

Note: 1. At EN 61326-1 (Industrial electromagnetic environment (EN/IEC 61326-1 Table 2))

2.No reset function is incorporated by any E5C2 model with ON/OFF control.The reset function is used to correct offset for proportional control. If there is an offset below the set value, turn the reset adjustment clockwise.

3.A special Watertight Cover is used to achieve this degree of protection (IP66, NEMA4). Refer to Y92A-□□N.

 

■ Connections

Connecting the Input

1.Connect a thermocouple, the E52-THE□Thermistor (replaceable element) or a platinum resistance thermometer to terminals 1 (positive) and 2 (negative) on the E5C2 as shown in thefollowing illustration.

 3.E5C4&E5C2 Series Temperature Controller.jpg

2.On the E52-□□1D, the lead wires are thermocouple element wires, making them difficult to solder because solder will not stick to them easily. Remove the crimp terminal and polish the ends before attempting to solder them.

 

Output

1.If the load circuit is a heating control system,be sure to connect the load to terminals 4 and 5.If the load circuit is a cooling control system,be sure to connect the load to terminals 4 and 6.

2.We recommend using an external relay to extend the electrical life of internal relays whendriving a large capacity load. This is particularly important when the output relay is switched frequently (e.g., with proportional control).

 

Power Supply

1.If a single power supply is used for the E5C2 and the load, the supply voltage of the power supply may vary greatly when the load is open or closed if the capacity of the power supply is not large enough. Make sure that the capacity of the power supply is large enough so that the supply voltage range will be always from 90% to 110% of the rated supply voltage.

2.The E5C2 operates at either 50 or 60 Hz.

 

Operation Indicator

Indicator

Output

NO contacts (4 and 5)

NC contacts (4 to 6)

Red Lit

ON

OFF

Not lit

OFF

ON

 

Dimensions

Note: All units are in millimeters unless otherwise indicated.

 5.E5C4&E5C2 Series Temperature Controller.jpg

Dimensions with Flush-mounting Adapter(Accessory),and Back Connecting Socket(Sold Separately)

 6.E5C4&E5C2 Series Temperature Controller.jpg

 7.E5C4&E5C2 Series Temperature Controller.jpg

■ Accessories (Order Separately)

Connection Sockets

P2CF-08 Front Connecting Socket

 8.E5C4&E5C2 Series Temperature Controller.jpg

P3G-08 Back Connecting Socket (for Flush Mounting)

 9.E5C4&E5C2 Series Temperature Controller.jpg

Hard Protective Cover

A Hard Protective Cover (Y92A-48B) is available. It can be used in the following cases.

1.To protect the setting section, against dust and dirt

2.To prevent accidently changing settings by touching the front of the Controller.

3.To protect the Controller from water drips

Appearance

 

Model

Y92A-48B

 

Safety Precautions

Refer to Safety Precautions for All Temperature Controllers.

■ Correct Use

 

Mounting

Track Mounting (E5C2 with P2CF-08)

When mounting two or more E5C2 models with track-mounting sockets, leave a space of approximately 20 mm on both sides of the sockets where hooks are located.

 10.E5C4&E5C2 Series Temperature Controller.jpg

Flush Mounting

Insert E5C2 into the square hole of the panel and insert an adapter from the back so that there will be no space between E5C2 and the panel. Then, secure the E5C2 with a screw.

 11.E5C4&E5C2 Series Temperature Controller.jpg

The P3G-08 can be wired in the same way as the P2CF-08.

 12.E5C4&E5C2 Series Temperature Controller.jpg

Dismounting

If flush mounted, loosen the screw of the adapter and disengage the hooks for dismounting.

 13.E5C4&E5C2 Series Temperature Controller.jpg

Temperature Setting

Do not turn the temperature setting knob of the E5C2 with excessive force, otherwise the stopper of the knob may break.

Others

1.Do not remove the housing of the E5C2, otherwise the housing may break.

2.To clean the surface of the E5C2, use a soft cloth wet with neutral detergent or alcohol. Do not use any organic solvent, such as paint thinner or benzine, strong acid or strong alkali to clean the surface of the E5C2, otherwise the surface of the E5C2 will become damaged.

E5C4&E5C2_01.jpgE5C4&E5C2_02.jpgE5C4&E5C2_03.jpgE5C4&E5C2_04.jpgE5C4&E5C2_05.jpgE5C4&E5C2_07.jpgE5C4&E5C2_08.jpgE5C4&E5C2_09.jpg

接线1.jpg

接线2.jpg面板解析.jpg

E5C4&E5C2_10.jpgE5C4&E5C2_11.jpgE5C4&E5C2_12.jpgE5C4&E5C2_13.jpgE5C4&E5C2_14.jpgE5C4&E5C2_15.jpgE5C4&E5C2_18.jpgE5C4&E5C2_19.jpg

E5C4&E5C2_20.jpgE5C4&E5C2_21.jpgE5C4&E5C2_22.jpgE5C4&E5C2_23.jpgE5C4&E5C2_24.jpgE5C4&E5C2_25.jpgE5C4&E5C2_26.jpg

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return